![Beckhoff TF6120 Manual Download Page 31](http://html.mh-extra.com/html/beckhoff/tf6120/tf6120_manual_2719284031.webp)
Configuration
TF6120
31
Version: 1.1
4.1.2.5
Schemata
Device-Parameters
Type
Req./Opt.
Description
Name
Req
Name for device like "PLC1". OPC-
Client browse this name
Description
Optional
AdsPort
Req
Number of ADS-PortID, like 801 for
first PLC-runtime system
AdsNetId
Optional
specific ADS-NetId, like
"174.12.15.45.1.1" Note:
If not specified or like "0.0.0.0.0.0",
the OPC-Server will always
communicate to AdsNetId of local
ADS-router
AdsTimeout
Optional
ADS timeout in ms for this ADS
device
AdsTimeSuspend
Optional
ADS suspend time in ms for this
ADS device, if the ads
communication fails
AutoCfg
Optional
0 : do not include symbol-file
defined under <AutoCfgSymFile>
1 : Include sym-file of TwinCAT-
PLC
defined under
<AutoCfgSymFile>
2 : Include sym-file of TwinCAT-
BCxxxx-project
defined under
<AutoCfgSymFile>
5 : Upload symbolic from ADS-
device
7 : Include tpy-file of TwinCAT28-
projec
t
defined under
<AutoCfgSymFile> 8 : Include tpy-
file of TwinCAT28-projec
t
defined
under <AutoCfgSymFile>, but
import only symbols with symbol-
property "OPC=1"
AutoCfgSymFile
Optional
full path and name of symbol-file to
be included like
"C:\Test\demo.sym" or "\
\User1\Test\demo.sym" or "C:
\User1\Test\demo.tpy"