The following table gives an overview about all possible configuration settings.
Parameter
Beschreibung
Name
Name of the device, e.g. PLC1. This will be the name
under which the device will be accessible for the
OPC-Client.
Description
[optional]
Optional description for the device.
AutoCfg
7 : All PLC variables are available via OPC 8 : Only a
subset of PLC variables is available via OPC
AutoCfgSymFile
Path to TPY-File, which is by default located in the
PLC project directory.
AdsPort
ADS port numer of the device, e.g. 851 for the first
PLC runtime.
AdsNetId
[optional]
Address of the ADS device. By default this is
0.0.0.0.0.0 for local system.
AdsTimeout
[optional]
Timeout for ADS connection to the device, measured
in [ms]. If the device is not reachable within that
timeframe, the OPC-Server returns BAD_QUALITY to
the OPC-Client.
AdsTimeSuspend
[optional]
Suspend time for the ADS device, measured in [ms].
If the ADS connection breaks, the OPC-Server waits
this time before sending the next ADS request to the
runtime.
Disable
[optional]
Deactivates the device.
Save the configuration via "File" --> "Save As". After the configuration has been saved, you will be asked if
this configuration should be set as the startup-configuration.