Configuration
TF6120
30
Version: 1.1
According to OPC Specification an OPC Server shall not update its cache automatically after writing a new
value. After a successful write operation the cached value remains the same and is not updated until the
next scan cycle. As this behaviour causes problems in some applications the Beckhoff OPC Server provides
an option to change this behaviour.
This option is turned off by default, so that the Beckhoff OPC Server operates correctly according to OPC
Specification. To change the cache update behaviour start the TwinCAT OPC Configurator, Open the "OPC
Server Settings" tab and check "AutoUpdateWriteCache"