Configuration
TF6120
42
Version: 1.1
• The opc-server is configured with a conversion "Factor 10" which is linked to this plc-variable.
• The opc-client gets the process value 20 Grad.
• If opc-client writes a new value 25 Grad celsius to OPC-server, the server will convert this to 250 and
writes this value to the PLC.
contains a PLC project and an OPC conversion definition.
Please note:
The OPC-Server presents a converted variable as data type "VT_R8 / Double" to OPC-client - independent
of the actual numerical datatyp in the PLC.
The usage of OPC-Conversions needs the configuration of a TPY-File (AutoCfgSymFile) for the
corresponding device and AutoCfg 8.
Step 1: Configuration of OPC-Conversions in OPC-Server
In the first step you need to configure TwinCAT OPC-Server for conversions. This is a one-time configuration
and does not need to be repeated when changes to the PLC project occur.
Start TwinCAT-OPC-Configurator
"Start - All Programs - TwinCAT System - TwinCAT OPC - TwinCAT
OPC Configurator"
Navigate to
"Conversions",
right click and select menue
"New"
.
For
"Name"
please enter a name for this alarm definition. This name has to be OPC conform, no special
characters allowed.With "OK" you see the dialog to configure in detail your new
"Conversion"
.