Fault correction
102
───
Version: 2.2
XTS
12.1.2
Error
12.1.2
ID
Message
Error
Number of the cause
0x8103
Undervoltage control voltage
24 V control voltage lower than 18.8 V
2
3
0x8104
Module overtemperature
Motor module temperature exceeds
75 °C, see: COE 9000:19…9000:1C
1
0x8105
PD-Watchdog
Process Data Watchdog:
XTS Task has not sent any new data
over three cycles
7
0x8109
Overvoltage control voltage
24 V control voltage higher than
28.8 V
8
0x810A
Peak overall backflow power
threshold exceeded
Calculated energy recovery power of
the motor module is too high
9
0x8403
ADC Error
ADC error
10
0x8404
Overcurrent Coil "x"
Current on coil "x" too high
11 12
0x8406
Undervoltage DC-Link
48 V power supply lower than 20 V
2
3
4
0x8407
Overvoltage DC-Link
48 V power supply higher than 56 V
2
5
0x8409
I2T - Motor module overload
Overload of the motor module at
105% I2T utilization rate:
105 % I2T utilization rate not reached
If 100 % I2T utilization rate is
reached: Current limited to nominal
current
6
0x840A
Overall current threshold ex-
ceeded
Total rated current of 16 A for the
power supply segment exceeded for
too long:
Short current peaks up to 48 A possi-
ble
13
0x840B
Peak overall current threshold
exceeded
48 A peak current of a power supply
segment exceeded
14
0x840C
Peak module overall backflow
current threshold exceeded
Current at the module sum current
measurement point changed too
quickly in the recovery direction
14