Fault correction
Version: 2.2
───
105
XTS
12.2.2
Error
12.2.2
ID
Message
Cause
Number of the solution
9000
Xts task cannot be accessed.
Is the context of the TcIoXts
driver set correctly?
Context setting in the "TcIoXtsDrv"
object incorrect
12
9001
Cycle time "x" µs of XTS task
is not supported! Set cycle
time to 250 µs.
Cycle time of the XTS task is not
equal to 250 µs:
A cycle time of 375 µs is also possi-
ble, but leads to losses of perfor-
mance and dynamics
1
9002
A XTS mover is lost at "y"
mm. Please restart TwinCAT
to perform a new detection.
Position "y" is at the transition from a
motor module to a power supply mod-
ule:
Incorrect order of the power supply
modules when configuring the XTS or
no reaction or defect of the motor
module at position "y"
8
9003
The motor module "x" with
name "y" has an error
Error on motor module "x"
13
9004
Out of memory. XTS mover
count is not supported.
Number of movers in use not sup-
ported
14
9005
TcIoXts driver has failed to
start up. Please check the
configuration and bootdata
files!
Driver cannot start
15
9006
Teaching file is invalid.
The stored teaching file does not
match the XTS system
Teaching file originates from a differ-
ent system
16
9007
Teaching data file "y" is cor-
rupt
The teaching file in the directory "C:
\TwinCAT\3.1\Target\Config\TcIoXts"
is corrupt or missing
4
9008
Teaching file of XTS module
"x" is invalid
Damaged or missing teaching file in
the directory:
"C:\TwinCAT\3.1\Target\Config
\TcIoXts"
Or motor module "x" not correctly
taught
4
9009
Saving of teaching file "Beze-
ichnungsstring" ("Designation
string") has failed
The teaching file "Bezeich-
nungsstring" ("Designation string")
could not be saved on the system
17
9010
Mover "x" is frozen at position
"y" mm
EtherCAT connection interrupted, po-
sition "y" is at the transition from a
motor module to a power supply mod-
ule
Incorrectly order of power supply
modules when configuring the XTS
8
9011
„…" cannot be loaded. Please
check that the installation is
correct
Driver cannot start
15
9012
Mover1 cannot be detected.
A general error occurs on
mover "x" during the detec-
tion process.
Mover 1 detection faulty, no mover 1
identified
18
9013
The SoftDrive "x" is not re-
sponding. Please check the
axis configuration or the Soft-
Drive version.
SoftDrive incorrectly linked or no suit-
able version of the SoftDrive driver for
the TwinCAT configuration
19