CAN
CX8050, CX8051 - Embedded-PCs for
CANopen and CAN
124
Version: 1.4
Example
Activate PDOs for bus node number 1, set inhibit time to 10ms (=100 x 100µs), set transmission type for
TxPDOs to 255, and set transmission type for RxPDOs to 1. The following telegram must be sent:
Id=0x601 DLC=8; Data=23 00 55 00 64 00 FF 01
The node responds with the following telegram:
Id=0x601 DLC=8; Data=60 00 55 00 00 00 00 00
Identifiers used
The default identifier allocation for the additional PDOs leaves the pre-defined regions for guarding, SDOs
etc. free, assumes a maximum of 64 nodes in the network with PDO6 as the next node, and proceeds
according to the following scheme:
Object
Function code
Resulting COB ID (hex)
Resulting COB ID (dec)
TxPDO5
1101
0x681 - 0x6BF
1665 - 1727
RxPDO5
1111
0x781 - 0x7BF
1921- 1983
TxPDO6
00111
0x1C1 - 0x1FF
449 - 511
RxPDO6
01001
0x241 - 0x27F
577 - 639
TxDPO7
01011
0x2C1 - 0x2FF
705 - 767
RxPDO7
01101
0x341 - 0x37F
833 - 895
TxPDO8
01111
0x3C1- 0x3FF
961 - 1023
RxPDO8
10001
0x441 - 0x47F
1089 - 1151
TxPDO9
10011
0x4C1 - 0x4FF
1217 - 1279
RxPDO9
10101
0x541 - 0x57F
1345 - 1407
TxDPO10
10111
0x5C1 - 0x5FF
1473 - 1535
RxPDO10
11001
0x641 - 0x67F
1601- 1663
TxPDO11
11011
0x6C1 - 0x6FF
1729 - 1791
RxPDO11
11101
0x741 - 0x77F
1857 - 1919
Attention
[Gefahrinformation hier einfügen!]
WarningEnsure that index 0x5500 is not used if Bus Couplers with more than 5 PDOs are
present in networks with node addresses > 64, otherwise identification overlaps can occur.
In that case, the PDO identifiers must be set individually.
For the sake of clarity, the default identifiers defined according to CANopen are also listed here:
Object
Function code
Resulting COB ID (hex)
Resulting COB ID (dec)
Emergency
0001
0x81 - 0xBF [0xFF]
129 - 191 [255]
TxPDO1
0011
0x181 - 0x1BF [0x1FF]
385 - 447 [511]
RxPDO1
0100
0x201 - 0x23F [0x27F]
513 - 575 [639]
TxPDO2
0101
0x281 - 0x2BF [0x2FF]
641 - 676 [767]
RxPDO2
0110
0x301 - 0x33F [0x37F]
769 - 831 [895]
TxDPO3
0111
0x381 - 0x3BF [0x3FF]
897 - 959 [1023]
RxPDO3
1000
0x401 - 0x43F [0x47F]
1025 - 1087 [1151]
TxPDO4
1001
0x481 - 0x4BF [0x4FF]
1153 - 1215 [1279]
RxPDO4
1010
0x501 - 0x53F [0x57F]
1281- 1343 [1407]
SDO (Tx)
1011
0x581 - 0x5BF [0x5FF]
1409 - 1471 [1535]
SDO (Rx)
1100
0x601 - 0x63F [0x67F]
1537 - 1599 [1663]
Guarding / Heartbeat/
Bootup
1110
0x701 - 0x73F [0x77F]
1793 - 1855 [1919]
The identifiers that result from the DIP switch settings on the coupler are given, as are the identifier regions
for the node addresses 64...127 (not settable in Bus Couplers BK5110, BK5120 and LC5100) in square
brackets. Addresses 1…99 can be set for the Fieldbus Box modules and the BK515x Bus Couplers.