6
1.6
Filling the pellet store
Fig. 2
Switching off FireWIN
Important information for system operators
The pellet flue-connected stove must be switched off
correctly
at least 15 minutes before the store is
filled – Fig. 2.
Press the ON/OFF button. Never switch off using the emergency OFF switch!
Pressing one of the six buttons firstly switches just the
lighting and display on. The boiler is only switched off
when the button is pressed for the 2nd time. Wait until
burnout mode has finished (not indicated on the display)
and open the combustion chamber doors.
During filling, negative pressure is created in the pellet
store and this can cause burn-back in the pellet boiler. The-
refore, the boiler must be stopped from operating during
the filling procedure.
Fig 2a
„Storage room fill“ sticker on the
storage room door
Every storage room fill should be documented by adding
the date and volume to the „Storage room fill“ sticker –
Fig. 2a.