![Baxi 35/80 IE Installation & Servicing Instructions Manual Download Page 46](http://html.mh-extra.com/html/baxi/35-80-ie/35-80-ie_installation-and-servicing-instructions-manual_2711660046.webp)
7. The pressure should be as quoted in
Section 4.0
Technical Data. If not, check that the gas
supply pressure is correct (Natural Gas 20mbar, Butane 30mbar and Propane 37mbar).
8. The pressure can be adjusted if required.
9. To check and set minimum pressure first remove one of the modulator wires.
Adjusting the Pressure
(
Fig 34
)
10. Remove the plastic protection cap from the pressure adjustment nuts on the valve.
11. The smaller nut (5mm) adjusts minimum pressure and the larger nut (8mm) maximum
pressure.
12. Using a suitable spanner adjust the relevant nut until the correct pressure is achieved.
13. Once the pressure has been set turn the boiler off and disconnect the pressure gauge.
14. Tighten the pressure test screw and refit the modulator to the valve. Reassemble in
reverse order.
Page 27
10.0 Completion
10.1 Completion
1. Hinge the facia panel upwards and refit the case front panel. Secure them with the screws
previously removed (
Fig. 37
).
Fig. 37
Summary of Contents for 35/80 IE
Page 15: ...F 190mm G 143mm ...
Page 20: ...Fig 5 ...
Page 51: ......
Page 55: ......
Page 57: ......
Page 59: ......
Page 67: ...br brown bk black b blue r red g green g y green yellow w white Page 39 14 0 Fault Finding ...
Page 69: ...Page 40 Fault Finding Solutions Sections A to E ...
Page 70: ...Page 41 ...
Page 71: ......
Page 73: ......
Page 74: ......