Return
Pressure Relief
Discharge
- 1/2"
Outercase Dimensions
Casing Height
-
780mm
Overall Height Inc
Flue Elbow
- 980mm
Casing Width
-
450mm
Casing Depth
-
345mm
Clearances
Both Sides
5 mm Min
Above Casing
200 mm Min
Below Casing
200 mm Min
Front 450
mm
Min (For
Servicing)
Front 5
mm
Min (In
Operation)
Weights
kg
Packaged Boiler
Carton
45
Packaged Flue Kit
3
Installation Lift
Weight
37
Central Heating Primary Circuit Pressures
bar
Safety Discharge
3
Max Operating
2.5
Min Operating
0.2
Recommend Operating
1-2
Pump
- Grundfos UP 15-60
Available Head
See graph below
Expansion Vessel
- (Integral with appliance)
bar
Min Pre-charge
Pressure
0.5
litre
Max Capacity of
CH System
125
Primary Water
1.0