Parameter
V-Controller (BUS 6 VC)
69
Baumüller Nürnberg Electronic GmbH & Co. KG
5.03047.01
P013
RFG
mode
The input selection chooses one out of four inputs of the ramp function generator and acti-
vates the set value limitation.
P002
RFG
input 1
P004
RFG
input 2
P006
RFG
input 3
All 3 inputs are balanced and can be written via the serial interface, position controller and
the set value generator as well as the analog set value input.
P003
RFG
ramp-up time 1
P005
RFG
ramp-up time 2
P007
RFG
ramp-up time 3
The acceleration assigned to the inputs can be set via the ramp-up times. The time selected
here correspond to a set value alteration of 100 %.
P010
RFG
ramp-down time 1
P011
RFG
ramp-down time 2
P012
RFG
ramp-down time 3
The deceleration assigned to the inputs can be set via the ramp-down times. The time selec-
ted here correspond to a set value alteration of 100 %.
P016
RFG
rounding
A first-order time delay element is implemented in order to round off ramp corners. The time
constants of the PT
1
device can be set by this parameter.
Bit no.
Meaning
0 ... 2
000: reserved
001: input 1
010: input 2
011: input 3
100: sum of input 1 and input 2
3
1: negative set values are disabled
4
1: positive set values are disabled
5
1: change polarity of actual set value
6 ... 15
reserved
NOTE
The value of P002 (RFG input) is changed automatically, when writing on P087 (PS Uzk nominal).
Summary of Contents for BUS 6 VC
Page 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Page 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Page 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 109: ......