Parameter
V-Controller (BUS 6 VC)
75
Baumüller Nürnberg Electronic GmbH & Co. KG
5.03047.01
P279
AI
1 scaling
P286
AI
2 scaling
These parameters enable scaling of the analog input variable.
The output values (see parameters P283, P290, P297, P304) of unsigned parameters are 0
till +100 % and of signed parameters are -100 % till +100 %. Which analog input voltage this
maximum values achieved depends on the scaling factor.
P280
AI
1 target Pxxx
P287
AI
2 target Pxxx
The receiver address for the output value can be set via this parameter.
P281
AI
1 offset
P288
AI
2 offset
These parameters can compensate for a possibly existing input voltage offset.
P282
AI
1 threshold value
P289
AI
2 threshold value
The sensitivity of the inputs can be set via the threshold values.
P283
AI
1 value
P290
AI
2 value
The AI value displays the respective current output value taking scaling and offset compen-
sation into consideration.
NOTE
No target parameter number check is carried out.
Summary of Contents for BUS 6 VC
Page 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Page 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Page 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 109: ......