Maintenance
92
V-Controller (BUS 6 VC)
5.03047.01
Baumüller Nürnberg Electronic GmbH & Co. KG
8.2
Error Messages
In the event of an error, parameter M error code (P124) indicates the appropriate error code. This error
is acknowledged when bit Reset disturbance in M control word (P120) is set from 0 to 1. If there is more
than one error, the system shows the next one immediately after acknowledgement.
!
Drive Manager Function Module (Error ID 00xx)
Error ID
Error Text
Meaning
Error reaction
Remedy
0001
hex
BASS protocol timeout
The communications source set in
P124 has not responded for longer
than the timeout set in P128.
Error reaction can be
set in P189
Check communications
(cables, daughterboard,
etc.)
0003
hex
Dual-Port RAM time-
out (cyclical data)
0004
hex
Dual-Port RAM time-
out (working data)
0005
hex
System boot procedure
An error was determined while
reading the boot data set from the
EEPROM. You can get more infor-
mation about the type of error by
referring to parameter DSM Mes-
sage (P192).
This disturbance usually occurs if
you replaced the controller firm-
ware with firmware that is incom-
patible.
Inhibit pulses imme-
diately
You should carefully
check the data set in the
controller’s RAM and then
program it in the EE-
PROM as the boot data
set.
0010
hex
Error switch (program
error)
Only for software development
Inhibit pulses imme-
diately
Summary of Contents for BUS 6 VC
Page 1: ...E 5 03047 01 Manual V Controller BUS 6 VC Specification Digital Control BUC ...
Page 4: ...Dokument Nr Document No 5 04058 01 Baumüller Nürnberg GmbH ...
Page 8: ...6 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 14: ...Technical Data 12 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 92: ...Parameter 90 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 108: ...Appendix 106 V Controller BUS 6 VC 5 03047 01 Baumüller Nürnberg Electronic GmbH Co KG ...
Page 109: ......