Requirements to the executing personnel
Instruction handbook
b maXX
5800
Document No. 5.16027.04
Baumüller Nürnberg GmbH
156
12.2
12.2 Requirements to the executing personnel
The personnel, who is appointed to setting out of operation, must have the required
knowledge and instructions, which is necessary for an execution according to the rules.
Select the personnel in such a way, that the safety instructions, which are mounted to the
device and its parts as well as to the connections, are understood and applied to.
12.3 Shutdown
Execute the setting out of operation as follows:
1
Put the device off-circuit and assure the device against unintentional restart.
2
Check the isolation from supply of all connections
(earliest 10 minutes after switching off).
3
Demount the connections and protect the connections according to the
safety instructions.
4
Document the shut down setting.
12.4 Demounting
m
Ensure that only qualified personnel, who are familiar with the safety notes and as-
sembly instructions, demount this device.
m
Wear safety shoes.
m
1
Secure the device against falling off/out.
2
Loosen all mechanical connections.
3
Lift the device out of the control cabinet.
4
Store the device in a suitable packing.
5
At transportation pay attention to, that the device is not damaged by wrong storage or
severe shocks, also refer to
What to observe when transporting
In case you want to dispose the device, additional data is available in chapter
NOTICE!
Note sharp edges.
In case, while installing, you lift a device with unprotected hands, fingers/palm can be
cut. If the device falls off, your feet can be cut up.
Therefore:
Wear safety gloves.