Shutdown, Storage
Instruction handbook
b maXX
5800
Document No. 5.16027.04
157
12
12.5 Storage conditions
m
Climatic category 1K4, Temperature range -25 °C to +55 °C
m
Reform the DC link capacitors:
n
by supplying the device ready-to-operate for at least 1 hour with supply voltage
n
but do not enable pulses during this time.
m
Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating reactor for this forming procedure. Devices, where no line commutating re-
actor is necessary can directly be supplied with mains voltage.
The device is maintenance-free. If you keep to the environmental conditions during the
entire period of storage, you can assume, that the device will not be damaged. In case
the environmental conditions during storage are not kept, you should assume that the de-
vice is damaged after storage.
12.6 Recommissioning
m
Reform the DC link capacitors:
n
by supplying the device ready-to-operate for at least one hour with
supply voltage
n
but do not transmit a pulse enable during this time.
m
Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating choke for this forming procedure. Devices, where no line commutating choke
is necessary can directly be supplied with mains voltage.
Execute commissioning as with a new device, refer to
CAUTION!
Property damage because of incorrect storage conditions
Incorrect storage can damage/destroy the device.
Therefore:
Assure, that the environmental conditions are kept during the entire period of storage:
CAUTION!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand
CAUTION!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand