5.5
Clearances to non-flammable walls
Caution:
Make sure there is a 3 mm clearance between the appliance and
the surrounding construction, to allow for expansion of the appliance during
use.
Put a non-flammable insulation plate between the appliance and the rear wall and side
wall according the figure hereunder.
Obey the requirements as mentioned in the table hereunder.
D
A
E
A
B
C
C
B
B
2
F
1
1
E
F
3
1
Non-flammable spacer
2
Non-flammable insulation plate
3
Non-flammable wall
Item
Dimension
A
Air gap
2 cm
B
Thickness plate
2.5 cm
C
Air gap / Spacer
2 cm
D
A+B+C
6.5 cm
E
B+C
4.5 cm
F
Minimum 3 mm clearance between appliance and surrounding construction
Clearances
Cuatro-7 75-60
23