May 22, 2023
EZ-SCREEN SLS Safety Light Curtain Instruction Manual
84
This system also is no longer redundant and may result in a loss of safety if the second safety switch fails to switch when
needed.
The circuits in either scenario do not inherently comply with the safety standard requirements of detecting single faults and
preventing the next cycle. In multiple-guard systems using series-connected positive-opening safety switches, it is important
to periodically check the functional integrity of each interlocked guard individually.
Operators, maintenance personnel, and others associated with the operation of the machine must be trained to recognize
such failures and be instructed to correct them immediately.
Open and close each guard separately while verifying that the
EZ-SCREEN SLS
outputs operate correctly throughout the
check procedure. Follow each gate closure with a manual reset, if needed. If a contact set fails, the
EZ-SCREEN SLS
will not
enable its reset function. If the
EZ-SCREEN SLS
does not reset, a switch may have failed; that switch must be immediately
replaced.
This check must be performed and all faults must be cleared, at a minimum, during periodic checkouts. If the application can
not exclude these types of failures and such a failure could result in serious injury or death, then the safety switches must not
be connected in series.
© Banner Engineering Corp.
Summary of Contents for EZ-SCREEN SLS
Page 16: ...May 22 2023 EZ SCREEN SLS Safety Light Curtain Instruction Manual 16 Banner Engineering Corp...
Page 52: ...Blank page 52...
Page 68: ...Blank page 68...
Page 90: ...Blank page 90...
Page 102: ...Blank page 102...
Page 106: ...Blank page 106...
Page 114: ...LinkedIn Twitter Facebook 2023 All rights reserved www bannerengineering com...