Secondary Device Functions (continued)
Alarm Enable
If the parameter is set (TRUE), the actual inclination
(degrees-difference or deviation) is compared with the
value of the alarm threshold. If the inclination is greater
than the threshold value, an event is created and sent.
Alarm Threshold
Threshold value of the inclination deviation for triggering an
event (see Fig. 5-10 on page 69).
Hysteresis taken into account, value is defined at
0° (upward) and −1° (downward).
– Values: 1…180
– Unit: Degrees (°)
– Default_Value: 10°
Alarm Teaching Status
Bit
Description
0
Device has not yet been taught-in, no reference
orientation set, inclination value not available.
1
Device has been taught-in, reference orientation
is set, inclination value is available.
Tab. 5-57: Inclination and installation aid – Alarm Teaching Status (R)
Use system command 0xC0 for teaching-in and defining
reference orientation.
The device cannot calculate the inclination until
the reference position has been taught-in.
Alarm Inclination Status
Bit
Description
0
Device is in its taught-in position/orientation.
1
Device is incorrectly oriented, inclination is equal
to or greater than the threshold value.
Tab. 5-58: Inclination and installation aid – Alarm Inclination Status (R)
Reference Taught Position
X-, Y-, Z-coordinate values of the reference position set
(taught-in) by system command 0x0C.
– Values: −16…+16, without vibrations, they should be in
the range −1…+1
– Unit: g (9.81 m/s
2
)
– Default: –
Inclination Deviation Value
Angle between the taught-in reference orientation and the
actual orientation:
– Values: 0…180
– Unit: Degrees (°)
5.12.5 System Commands
System Commands for teaching-in and defining the
reference orientation.
The device cannot calculate the inclination until
the reference position has been taught-in.
Command Value Device Action
0xC0 (192)
Set Reference Orientation
– Sets
the reference orientation of the
actual position of the device.
Responses: ACK: command
successful, reference stored.
0x81 (129)
Application Reset
– Resets the
inclination alarm configuration to the
default value of the firmware.
0x82 (130)
Reset Factory Settings
– Resets the
inclination alarm configuration to the
default value of the firmware.
Tab. 5-59: Inclination and installation aid – System Commands
5.12.6 Events
Event
Code
Event
Type
Description
Device Status
0x8CD0
(36048)
Warning
Inclination
alarm
►
Check
installation.
1 –
Maintenance-
Required
Tab. 5-60: Inclination and installation aid – Events
This event shows that the device (sensor) has lost its
original position (taking the threshold value into account).
The fastening of the device (sensor) should be checked.
The device is still functional, but the measured values
could be invalid, since the sensor, e.g., cannot perform any
optical measurements because it has lost the receiver/
transmitter light signal.
BOS R254K-UUI-LH10-S4
Photoelectric Sensors
Summary of Contents for BOS R254K-UUI-LH10-S4
Page 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R254K UUI LH10 S4...
Page 2: ...www balluff com...
Page 3: ...BOS R254K UUI LH10 S4 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 99: ...BOS R254K UUI LH10 S4 IO Link Configuration english...
Page 100: ...www balluff com...
Page 195: ......