74
english
5.13.4 ISDU
Name
Index
Subindex
Access
Length
Data Type
Data
Storage
Default
Vibration
Level
0x210E
(8462)
0
R
4
Float32
No
–
Vibration
Alarm
Configuration
0x210F
(8463)
0
R/W
5
Record
Yes
–
Vibration
Alarm Enable
1
R/W
1
BOOL
No
0
Vibration
Alarm
Threshold
2
R/W
4
Float32
No
0.0
Vibration
Alarm Status
0x2110
(8464)
0
R
1
BOOL
No
–
Tab. 5-64: Vibration detection – ISDU
Vibration Level
Vibration level, primarily the calculated v-RMS value (root
mean square)
Unit: [mm/s]
Minimum value: 0.0
Maximum value: 1770.0
Vibration Alarm Enable
If the parameter is set (TRUE), the vibration level is
compared with the vibration alarm threshold value. If the
vibration exceeds the threshold value, an event is created
and sent.
0 = alarm deactivated
1…255 = alarm activated
Default = 0
Vibration Alarm Threshold
Threshold value of the vibration for triggering an event. The
comparison is performed for each axis and variable with
logical OR-link.
The hysteresis is fixed and is based on time (not on
amplitude). If the vibration value exceeds the threshold
value for 50 ms, the alarm is activated. Objective:
debouncing and avoidance of shock values.
Unit: [mm/s]
Minimum value: 0.0
Maximum value: 1770.0
Vibration Alarm Status
The status flag is TRUE if the vibration exceeds the alarm
threshold value.
0 = no alarm
255 = alarm
5.13.5 Events
Event
Code
Event
Type
Description
Device Status
0x8CD1
(36049)
Warning
Vibration alarm
►
Check
machine.
0 – Device is
operating
properly
Tab. 5-65: Vibration detection – Events
This event indicates that the measured vibration value
(v-RMS) exceeds the specified threshold value. The
machine should be inspected, since the vibration value is
above the normal value. The status of the device (sensor)
itself is ok, it is functioning properly.
The higher vibration is caused outside of the device. The
primary goal is the detection of trends, changes to the
vibration alarm value (see Fig. 5-11 on page 73 yellow
line).
5
Secondary Device Functions (continued)
BOS R254K-UUI-LH10-S4
Photoelectric Sensors
Summary of Contents for BOS R254K-UUI-LH10-S4
Page 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R254K UUI LH10 S4...
Page 2: ...www balluff com...
Page 3: ...BOS R254K UUI LH10 S4 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 99: ...BOS R254K UUI LH10 S4 IO Link Configuration english...
Page 100: ...www balluff com...
Page 195: ......