5.13.4 ISDU
Name
Index
Subindex
Access
Length
Data Type Data Storage
Default
Vibration Level
0x210E (8462)
0
R
4 Byte
FLOAT32
n/a
–
Vibration Alarm
Configuration
0x210F (8463)
0
R/W
5 Byte
Yes
Vibration Alarm Enable
1
R/W
1 Byte
BOOL
No
0
Vibration Alarm Threshold
2
R/W
4 Byte
FLOAT32
No
0.0
Vibration Alarm Status
0x2110 (8464)
0
R
1 Byte
BOOL
n/a
–
Tab. 5-63: Vibration detection – ISDU
Vibration Level
Vibration level, primarily the calculated v-RMS value (root
mean square)
Unit: [mm/s]
Minimum value: 0.0
Maximum value: 1770.0
Vibration Alarm Enable
If the parameter is set (TRUE), the vibration level is
compared with the vibration alarm threshold value. If the
vibration exceeds the threshold value, an event is created
and sent.
0 = alarm deactivated
1…255 = alarm activated
Default = 0
Vibration Alarm Threshold
Threshold value of the vibration for triggering an event. The
comparison is performed for each axis and variable with
logical OR-link.
The hysteresis is fixed and is based on time (not on
amplitude). If the vibration value exceeds the threshold
value for 50 ms, the alarm is activated. Objective:
debouncing and avoidance of shock values.
Unit: [mm/s]
Minimum value: 0.0
Maximum value: 1770.0
Vibration Alarm Status
The status flag is TRUE if the vibration exceeds the alarm
threshold value.
0 = no alarm
255 = alarm
5.13.5 Events
Event
Code
Event
Type
Description
Device Status
0x8CD1
(36049)
Warning
Vibration alarm
►
Check
machine.
0 – Device is
operating
properly.
Tab. 5-64: Vibration detection – Events
This event indicates that the measured vibration value
(v-RMS) exceeds the specified threshold value. The
machine should be inspected, since the vibration value is
above the normal value. The status of the device itself is
OK, it is functioning properly.
The higher vibration is caused outside of the device. The
primary goal is the detection of trends, changes to the
vibration alarm value (see Fig. 5-11 on page 82 yellow
line).
5
Secondary Device Functions (continued)
BOS R080K-UIM-RE10-…
Photoelectric Sensors
Summary of Contents for BOS R080K-UIM-RE10 Series
Page 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R080K UIM RE10...
Page 2: ...www balluff com...
Page 3: ...BOS R080K UIM RE10 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 107: ...BOS R080K UIM RE10 IO Link Configuration english...
Page 108: ...www balluff com...
Page 211: ......