30
english
Switchpoint Mode
The AdSS profile only supports one switching
point (setpoint). Accordingly, only the Single Point
Mode is available in this profile.
In the LSSC profile, the hysteresis can be set
between 1 and 10 percent with respect to the
taught-in 100 % reference.
Single Point Mode
In Single Point Mode, only one switching point (setpoint) is
defined.
Switching behavior:
– Measurement value ≥ switching point: output active
– Measurement value ≤ switching point minus a defined
hysteresis: output inactive
Fig. 4-3:
High
SP1
SP1-Hys
Low
Measurement value
Switching output
Single-Point Mode
Two-Point Mode
In Two-Point Mode, two switching points (setpoints) are
defined.
Switching behavior:
– Measurement value ≥ switching point 1: output active
– Measurement value ≤ switching point 2: output inactive
Fig. 4-4:
High
SP1
SP2
Low
Measurement value
Switching output
Two-Point Mode
4
Primary Device Functions (continued)
Window Mode
In Window Mode, two switching points (setpoints) are
defined.
Switching behavior:
– If the output is inactive and the measurement value is
greater than or equal to switching point 2 + 50% of the
set hysteresis or the measurement value is less than or
equal to switching point 1 – 50% of the set hysteresis,
the output switches to active.
– If the output is active and the measurement value is
less than or equal to switching point 2 – 50% of the set
hysteresis or the measurement value is greater than or
equal to switching point 1 + 50% of the set hysteresis,
the output switches to inactive.
Fig. 4-5:
High
SP1
SP2
Hyst.
Hyst.
Low
Measurement
value
Switching output
Window Mode
Teach Process
For a successful teach-in as well to directly set a setpoint,
the following conditions must be met:
– The setpoint that is to be taught must be in the validity
range of the measurement value signal.
Additionally in Two-Point and Window Mode:
– Setpoint 1 must be greater than setpoint 2.
– The distance between the setpoints must be greater
than or equal to the minimum hysteresis.
Due to the requirements listed above, it may be
necessary to vary the order of the setpoints for a
successful teach-in.
An active teach process in indicated by illumination of the
red LED. If the red LED flashes, the currently pending
measurement value is outside of the validity range (IO-Link
process) or a manual teach was not possible.
BOS R080K-UIM-RE10-…
Photoelectric Sensors
Summary of Contents for BOS R080K-UIM-RE10 Series
Page 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R080K UIM RE10...
Page 2: ...www balluff com...
Page 3: ...BOS R080K UIM RE10 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 107: ...BOS R080K UIM RE10 IO Link Configuration english...
Page 108: ...www balluff com...
Page 211: ......