www.balluff.com
27
english
6
IO-Link interface (continued)
6.2.8 Ambient pressure
The sensor is equipped with ambient pressure monitoring
(index 0x2049 (8265)). The ambient pressure
(subindex 0x01 (1)) and the minimum and maximum values
since the last startup (subindex 0x02 (2) and 0x03 (3)),
since production (subindex 0x04 (4) and 0x05 (5)) and
since the last manual reset (subindex 0x06 (6) and 0x07
(7)) are measured. The values in index 0x2049 (8265),
subindex 0x02 (2), 0x03 (3), 0x06 (6) and 0x07 (7) can be
reset for all modules simultaneously by means of a
maintenance reset (see Section
page 41) or induvidually for the ambient pressure (see
A lower threshold (index 0x204A (8266) subindex 0x01 (1))
and an upper threshold (index 0x204A (8266)
subindex 0x02 (2)) can be defined for the ambient pressure
module. The sensor recognizes when a threshold is
exceeded and sets the Boolean variables for
undershooting the lower threshold (index 0x204B (8267)
subindex 0x01 (1)) or for exceeding the upper threshold
(index 0x204B (8267) subindex 0x02 (2)). These Boolean
variables are available in the status bits of the process data
Additionally, the sensor can trigger IO-Link events if a
threshold is exceeded. The sending of events (see
Tab. 6-21 on page 40) for monitoring the ambient
pressure can be switched off (index 0x204A (8266)
subindex 0x03 (3)).
Index
Sub-
index
Access Description
Data
type
Value
range
Default
value
AMBIENT PRESSURE
1)
0x2049
(8265)
0x01
(1)
Read
only
AMBIENT PRESSURE – Current value in hPa
float32
0x02
(2)
Read
only
MINIMUM AMBIENT PRESSURE SINCE STARTUP
– Minimum value since last startup in hPa
float32
0x03
(3)
Read
only
MAXIMUM AMBIENT PRESSURE SINCE STARTUP
– Maximum value since last startup in hPa
float32
0x04
(4)
Read
only
MINIMUM AMBIENT PRESSURE LIFETIME –
Minimum value since production in hPa
float32
0x05
(5)
Read
only
MAXIMUM AMBIENT PRESSURE LIFETIME –
Maximum value since production in hPa
float32
0x06
(6)
Read
only
MINIMUM AMBIENT PRESSURE SINCE RESET –
Minimum value since last manual reset in hPa
float32
0x07
(7)
Read
only
MAXIMUM AMBIENT PRESSURE SINCE RESET
– Maximum value since last manual reset in hPa
float32
AMBIENT PRESSURE ALARM CONFIGURATION
1)
0x204A
(8266)
0x01
(1)
Read/
Write
LOWER ALARM LEVEL AMBIENT PRESSURE –
Lower threshold for ambient pressure in hPa
float32
300…1100
[hPa]
300 [hPa]
0x02
(2)
Read/
Write
UPPER ALARM LEVEL AMBIENT PRESSURE –
Upper threshold for ambient pressure in hPa
float32
300…1100
[hPa]
1100 [hPa]
0x03
(3)
Read/
Write
ENABLE ALARM AMBIENT PRESSURE – Activates
(True) or deactivates (False) the sending of IO-Link
events 0x8CEA and 0x8CEB if one of the thresholds
is exceeded or underrun
bool
True/False
True
AMBIENT PRESSURE ALARM STATUS
1)
0x204B
(8267)
0x01
(1)
Read
only
LOWER ALARM STATUS AMBIENT PRESSURE
– Lower threshold underrun
bool
0x02
(2)
Read
only
UPPER ALARM STATUS AMBIENT PRESSURE
– Upper threshold exceeded
bool
Tab. 6-12: Ambient pressure
1)
only for the BCM R15E-
002
-DI00-_ _ , _-S4
1)
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Summary of Contents for BCM R15E-00 Series
Page 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Page 2: ...www balluff com...
Page 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Page 50: ...www balluff com...
Page 95: ......