40
english
6
IO-Link interface (continued)
6.4
Event list
Module
Event
code
Characte-
ristic
Meaning
DEVICE
TEMPERATURE
1)
0x4000
(16384)
Error
TEMPERATURE FAULT - OVERLOAD – The temperature has exceeded the
specified maximum temperature. The heat source must be removed.
0x4210
(16912)
Warning
DEVICE TEMPERATURE OVER-RUN - CLEAR SOURCE OF HEAT – Danger
of damage to device. Device is too hot. Remove heat source.
0x4220
(16928)
Warning
DEVICE TEMPERATURE UNDER-RUN – INSULATE DEVICE – Danger of
damage to device. Device is too cold.
0x8D10
(36112)
Warning
DEVICE TEMPERATURE LOWER ALARM – The configured lower
temperature alarm threshold is underrun.
0x8D20
(36128)
Warning
DEVICE TEMPERATURE UPPER ALARM – The configured upper
temperature alarm threshold is exceeded.
CONTACT
TEMPERATURE
0x8CE0
(36064)
Warning
CONTACT TEMPERATURE LOWER ALARM – The configured lower
temperature alarm threshold is underrun.
0x8CE1
(36065)
Warning
CONTACT TEMPERATURE UPPER ALARM – The configured upper
temperature alarm threshold is exceeded.
HUMIDITY
1)
0x8CE5
(36069)
Warning
HUMIDITY LOWER ALARM – The configured lower humidity alarm threshold
is underrun.
0x8CE6
(36070)
Warning
HUMIDITY UPPER ALARM – The configured upper humidity alarm threshold
is exceeded.
AMBIENT
PRESSURE
1)
0x8CEA
(36074)
Warning
AMBIENT PRESSURE LOWER ALARM – The configured lower ambient
pressure alarm threshold is underrun.
0x8CEB
(36075)
Warning
AMBIENT PRESSURE UPPER ALARM – The configured upper ambient
pressure alarm threshold is exceeded.
VIBRATION
0x8CF0
(36080)
Notification SEVERITY ZONE CHANGE – The degree of severity of the vibration has
reached a different zone.
0x8CF1
(36081)
Warning
PRE-ALARM v-RMS – The RMS value of vibration velocity has exceeded the
configured pre-alarm threshold for magnitude or at least one axis.
0x8CF2
(36082)
Warning
MAIN-ALARM v-RMS – The RMS value of vibration velocity has exceeded
the configured main-alarm threshold for magnitude or at least one axis.
0x8CF3
(36083)
Warning
PRE-ALARM a-RMS – The RMS value of vibration acceleration has
exceeded the configured pre-alarm threshold for magnitude or at least one
axis.
0x8CF4
(36084)
Warning
MAIN-ALARM a-RMS – The RMS value of vibration acceleration has
exceeded the configured main-alarm threshold for magnitude or at least one
axis.
1)
only for BCM R15E-
002
-DI00-_ _ , _-S4
Tab. 6-21: Event list
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Summary of Contents for BCM R15E-00 Series
Page 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Page 2: ...www balluff com...
Page 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Page 50: ...www balluff com...
Page 95: ......