36
english
6
IO-Link interface (continued)
Application choice (APPLICATION TYPE)
Index 0x2101 (8449) can be used to select the application
monitored by BCM. The parameters for vibration
monitoring are set to the values from Tab. 6-15.
Subindices that are not listed are not changed by any
profile.
APPLICATION TYPE (index 0x2101 (8449), subindex 0x00 (0))
0
1
2
3
4
5
6
7
ISO 10816-3 gr
oup 1, rigid
ISO 10816-3
gr
oup 1,
flexible
ISO 10816-3 gr
oup 2, rigid
ISO 10816-3
gr
oup 2,
flexible
Sequential machine,
normal
Sequential machine,
fast
Sequential machine,
very fast
Custom
configuration
Identifier (subindex)
Value
TIME WINDOW VIBRATION (index 0x2102 (8450))
TIME WINDOW VIBRATION
(0x00 (0))
4: 1000
[ms]
4: 1000
[ms]
4: 1000
[ms]
4: 1000
[ms]
2: 250
[ms]
1: 100
[ms]
0: 20
[ms]
No
change
VIBRATION CONFIGURATION (index 0x2103 (8451))
EVENT RESPONSE DELAY
(0x01 (1))
5000
[ms]
5000
[ms]
5000
[ms]
5000
[ms]
1000
[ms]
400
[ms]
100
[ms]
No
change
LOWER BANDWIDTH LIMIT
(0x02 (2))
10 [Hz]
10 [Hz]
10 [Hz]
10 [Hz]
10 [Hz]
20 [Hz]
100 [Hz]
UPPER BANDWIDTH LIMIT
(0x03 (3))
1000
[Hz]
1000
[Hz]
1000
[Hz]
1000
[Hz]
3199
[Hz]
3199
[Hz]
3199
[Hz]
VIBRATION VELOCITY ALARM CONFIGURATION ADVANCED (index 0x2107 (8455))
PRE-ALARM-LEVEL v-RMS X
(0x01 (1))
4.5
[mm/s]
7.1
[mm/s]
2.8
[mm/s]
4.5
[mm/s]
No change
MAIN-ALARM-LEVEL v-RMS X
(0x02 (2))
7.1
[mm/s]
11.0
[mm/s]
4.5
[mm/s]
7.1
[mm/s]
PRE-ALARM-LEVEL v-RMS Y
(0x03 (3))
4.5
[mm/s]
7.1
[mm/s]
2.8
[mm/s]
4.5
[mm/s]
MAIN-ALARM-LEVEL v-RMS Y
(0x04 (4))
7.1
[mm/s]
11.0
[mm/s]
4.5
[mm/s]
7.1
[mm/s]
PRE-ALARM-LEVEL v-RMS Z
(0x05 (5))
4.5
[mm/s]
7.1
[mm/s]
2.8
[mm/s]
4.5
[mm/s]
MAIN-ALARM-LEVEL v-RMS Z
(0x06 (6))
7.1
[mm/s]
11.0
[mm/s]
4.5
[mm/s]
7.1
[mm/s]
PRE-ALARM-LEVEL v-RMS
MAGNITUDE (0x07 (7))
4.5
[mm/s]
7.1
[mm/s]
2.8
[mm/s]
4.5
[mm/s]
MAIN-ALARM-LEVEL v-RMS
MAGNITUDE (0x08 (8))
7.1
[mm/s]
11.0
[mm/s]
4.5
[mm/s]
7.1
[mm/s]
VIBRATION SEVERITY ZONE CONFIGURATION (index 0x2108 (8456))
SEVERITY ZONE BOUNDARY
A/B (0x01 (1))
2.3
[mm/s]
3.5
[mm/s]
1.4
mm/s
2.3
[mm/s]
No change
SEVERITY ZONE BOUNDARY
B/C (0x02 (2))
4.5
[mm/s]
7.1
[mm/s]
2.8
mm/s
4.5
[mm/s]
SEVERITY ZONE BOUNDARY
C/D (0x03 (3))
7.1
[mm/s]
11.0
[mm/s]
4.5
mm/s
7.1
[mm/s]
Tab. 6-15: Vibration monitoring parameter depending on the selected
profile
When manually changing a parameter listed
here, the user-defined profile is configured
automatically and all parameters are transferred
to it.
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Summary of Contents for BCM R15E-00 Series
Page 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Page 2: ...www balluff com...
Page 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Page 50: ...www balluff com...
Page 95: ......