![Balluff BCM R15E-00 Series User Manual Download Page 85](http://html1.mh-extra.com/html/balluff/bcm-r15e-00-series/bcm-r15e-00-series_user-manual_3618085085.webp)
www.balluff.com
37
english
6
IO-Link interface (continued)
Time window of the vibration module
(TIME WINDOW VIBRATION)
Index 0x2102 (8450) can be used to select the time
window for the vibration module over which the statistical
evaluation of the signal takes place. The time window,
depending on the selected value, is entered in Tab. 6-16.
When choosing the time window, note that the
frequency of the signal must not be less than a
minimum frequency as defined in Tab. 3-3 on
page 11. When setting the time window and
when setting the lower band limit of the
bandpass filter, invalid values are rejected with
error code 0x8040 (32832) or 0x8041 (32833).
The bandpass filter can be configured using
index 0x2103 (8451) (see page 28).
Value
Time window
0x00 (0)
20 ms
1)
0x01 (1)
100 ms
1)
0x02 (2)
250 ms
0x03 (3)
500 ms
0x04 (4)
1000 ms
1)
This time window is not compatible with the default value for the lower
band limit. Observe note!
Tab. 6-16: Time window configuration
Severity zone (SEVERITY ZONE)
The variable stored in index 0x2117 (8471) subindex 0x00
(0) indicates the current degree of severity of vibration. The
boundaries of the severity zones can be configured in
index 0x2108 (8456).
Variable content
Severity zone
0b00
Zone A
0b01
Zone B
0b10
Zone C
0b11
Zone D
Tab. 6-17: Severity zone
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Summary of Contents for BCM R15E-00 Series
Page 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Page 2: ...www balluff com...
Page 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Page 50: ...www balluff com...
Page 95: ......