Process data profile (PROCESS DATA PROFILE)
Index 0x2000 (8192) subindex 0x00 (0) defines the
process data profile. The profiles are explained in Section
Value of
PROCESS
DATA PROFILE
Selected profile
1
VIBRATION VELOCITY
2
VIBRATION VELOCITY PEAK-TO-
PEAK
3
VIBRATION ACCELERATION
4
VIBRATION ACCELERATION PEAK-
TO-PEAK
5
ENVIRONMENTAL
1)
8
CUSTOM PROCESS DATA
PROFILE
2)
1)
only for the BCM R15E-
002
-DI00-_ _ , _-S4
2)
The CUSTOM PROCESS DATA PROFILE can be configured in
index 0x2001 (8193).
Tab. 6-4: Process data profiles
6
IO-Link interface (continued)
User-defined process data profile (CUSTOM
PROCESS DATA PROFILE CONFIGURATION)
Index 0x2001 (8193) defines the user-defined process data
profile: each slot is configured in a subindex. Slot 1 is
configured in the first subindex, slot 2 is configured in the
second, slot 3 in the third and slot 4 in the fourth subindex.
The subindices 0x01 (1) to 0x04 (4) can be identically
configured according to Tab. 6-5.
Byte 0
Byte 1
Byte 2
Byte 3
MSB index
LSB index
Sub index
0x00 (0)
Tab. 6-5: Byte meaning of the subindices from CUSTOM PROCESS
DATA PROFILE CONFIGURATION
This enables the analysis variables that are available in the
service data to be applied to the process data. The status
bits are held in place in a 5th slot.
All possible values for the process data are listed in
Example:
If the contact temperature is to be applied to slot 2 and the
v-RMS magnitude is to be applied to slot 4, the byte
sequence 0x20 (32) 0x31 (49) 0x01 (1) 0x00 (0) for the
contact temperature must be written to subindex 0x02 (2)
and the byte sequence 0x21 (33) 0x14 (20) 0x04 (4) 0x00
(0) for the v-RMS magnitude must be written to subindex
0x04 (4). These values can both be taken from Tab. 6-6 as
well as determined from the indices of the service data.
The contact temperature is in index 0x2031 (8241),
subindex 0x01 (1). Therefore, bytes 0x20 (32) 0x31 (49)
0x01 (1) 0x00 (0) must be written to the corresponding
subindex.
Fig. 6-1:
Byte 0:
0x20 (32)
1
0x01 (1)
2
0x2001
(8193)
3
0x03 (3)
0x02 (2)
4
0x04 (4)
Byte 1:
0x31 (49)
Byte 2:
0x01 (1)
Byte 3:
0x00 (0)
0x2031 (8241)
CUSTOM PROCESS DATA PROFILE CONFIGURATION
0x01 (1)
Contact temperature (CONTACT TEMPERATURE)
Index
Sub index
Sub index
Index
Write in user-defined process data profile
Slot
Defining the contact temperature in any slot in the user-
defined process data profile
BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
Summary of Contents for BCM R15E-00 Series
Page 1: ...BCM R15E 00_ DI00 _ _ _ S4 deutsch Betriebsanleitung english User s guide...
Page 2: ...www balluff com...
Page 3: ...BCM R15E 00_ DI00 _ _ _ S4 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 49: ...BCM R15E 00_ DI00 _ _ _ S4 User s Guide english...
Page 50: ...www balluff com...
Page 95: ......