www.baldormotion.com
6-6 Troubleshooting
MN1941
6.2.7 Ethernet
Cannot connect to the controller over TCP/IP:
H
Check that there is not an EPL manager node (for example NextMove
e
100 with node ID
240) on the network. If there is a manager node on the network, then an EPL compatible
router must be used to allow TCP/IP communication on the EPL network.
H
Check that the PC’s Ethernet adapter has been correctly configured, as described in section
5.2.4.
The ETHERNET Powerlink network does not seem to be operating correctly:
H
Confirm that only one device on the network is set to be the ETHERNET Powerlink manager
node (node ID 240, selector switches LO = F, HI = 0).
H
Confirm that the reference source on all controlled nodes has been set to EPL in the Mint
WorkBench Operating Mode Wizard, and that the manager node has been configured
correctly. For a NextMove
e
100 manager node, this requires the System Configuration
Wizard to be used in Mint WorkBench.
H
Confirm that each device on the network has a different node ID.
H
Confirm that there are no more than 10 ‘daisy-chained’ devices on each branch of the
network.
6.2.8 CANopen
The CANopen bus is ‘passive’:
This means that the internal CAN controller in the NextMove
e
100 is experiencing a number of
Tx and/or Rx errors, greater than the passive threshold of 127. Check:
H
12-24 V is being applied between pin 9 (+24 V) and pin 6 or 3 (0 V) of the CAN connector, to
power the opto-isolators.
H
There is at least one other CANopen node in the network.
H
The network is terminated
only
at the ends, not at intermediate nodes.
H
All nodes on the network are running at the same baud rate.
H
All nodes have been assigned a unique node ID.
H
The integrity of the CAN cables.
The NextMove
e
100 should recover from the ‘passive’ state once the problem has been rectified
(this may take several seconds).
The CANopen bus is ‘off’:
This means that the internal CAN controller in the NextMove
e
100 has experienced a fatal
number of Tx and/or Rx errors, greater than the off threshold of 255. At this point the node will
have switched itself to a state whereby it cannot influence the bus. Check:
H
12-24 V is being applied between pin 9 (+24 V) and pin 6 or 3 (0 V) of the CAN connector, to
power the opto-isolators.
H
There is at least one other CANopen node in the network.
H
The network is terminated
only
at the ends, not at intermediate nodes.
H
All nodes on the network are running at the same baud rate.
H
All nodes have been assigned a unique node ID.
H
The integrity of the CAN cables.
To recover from the ‘off’ state, the source of the errors must be removed and bus then reset. This
can be done using the Mint
BUSRESET
keyword, or by resetting the NextMove
e
100.
Summary of Contents for NXE100-1608Dx
Page 1: ......
Page 2: ......
Page 16: ...www baldormotion com 3 4 Basic Installation MN1941 ...
Page 50: ...www baldormotion com 4 34 Input Output MN1941 ...
Page 77: ...www baldormotion com Operation 5 27 MN1941 Figure 37 The NextMove e100 servo loop ...
Page 98: ...www baldormotion com 6 8 Troubleshooting MN1941 ...
Page 110: ...Index MN1941 ...
Page 112: ...Comments MN1941 Thank you for taking the time to help us ...
Page 113: ......
Page 114: ......