www.baldormotion.com
B-2 CE Guidelines
MN1941
B.1.3 Use of CE compliant components
The following points should be considered:
H
Using CE approved components will not guarantee a CE compliant system!
H
The components used in the controller, installation methods used, materials selected for
interconnection of components are important.
H
The installation methods, interconnection materials, shielding, filtering and earthing /
grounding of the system as a whole will determine CE compliance.
H
The responsibility of CE mark compliance rests entirely with the party who offers the end
system for sale (such as an OEM or system integrator).
B.1.4 EMC installation suggestions
To ensure electromagnetic compatibility (EMC), the following installation points should be
considered to help reduce interference:
H
Earthing/grounding of all system elements to a central earth/ground point (star point).
H
Shielding of all cables and signal wires.
B.1.5 Wiring of shielded (screened) encoder cables
1
6
2
7
3
8
9
5
NextMove
e
100
X5 / X6 / X7
Encoder Connector
Housing
Cable
Twisted pairs
Connect overall shield
to connector backshell.
Connect overall shield
to connector backshell.
CHA+
CHA-
CHB+
CHB-
CHZ+
CHZ-
+5V
GND
Figure 43 - Encoder signal cable grounding
Summary of Contents for NXE100-1608Dx
Page 1: ......
Page 2: ......
Page 16: ...www baldormotion com 3 4 Basic Installation MN1941 ...
Page 50: ...www baldormotion com 4 34 Input Output MN1941 ...
Page 77: ...www baldormotion com Operation 5 27 MN1941 Figure 37 The NextMove e100 servo loop ...
Page 98: ...www baldormotion com 6 8 Troubleshooting MN1941 ...
Page 110: ...Index MN1941 ...
Page 112: ...Comments MN1941 Thank you for taking the time to help us ...
Page 113: ......
Page 114: ......