3-18 Basic Installation
MN1902
3.5.4 Thermal switch connection
You might wish to wire the motor’s thermal switch contacts (normally open), using a relay, to a
digital input on connector X3 (see section 4.3.1). Using the WorkBench v5 Digital I/O tool, the
input can be configured to be the motor trip input. This allows the FlexDrive
II
to respond to
motor over-temperature conditions. The Mint keyword
MOTORTEMPERATUREINPUT
can also
be used to configure a digital input for this purpose. A typical circuit, using DIN1 as the input,
is shown in Figure 9.
A
B
motor
thermal
switch
CREF
X3
7
DIN0 (
INX.0
)
Relay
Customer
supplied
24VDC
supply
+24VDC
0V
10
11
12
13
14
15
16
17
DIN1 (
INX.1
)
DIN3 (
INX.3
)
DIN7 (
INX.7
)
DIN5 (
INX.5
)
DIN4 (
INX.4
)
DIN2 (
INX.2
)
DIN6 (
INX.6
)
Separate
customer
supplied
24VDC supply
+24VDC
0V
Figure 9 - Motor thermal switch circuit
CAUTION
: The 24VDC power supply connected to the thermal switch must be a
separate supply as shown in Figure 9. Do not use the 24V supply used
for the drive enable signal, or the internally generated supply (if present).
The thermal switch wires often carry noise that could cause erratic drive
operation or damage. The thermal switch contacts must never be wired
directly to a digital input.
The separate 24VDC supply used for the thermal switch may also be
used for the motor brake circuit (section 3.5.5).
Summary of Contents for Flex+DriveII
Page 1: ...FlexDriveII Flex DriveII Servo Controls SERVO DRIVE Installation Manual 10 02 MN1902...
Page 2: ......
Page 14: ...2 4 Introduction MN1902...
Page 68: ...4 20 Input Output MN1902...
Page 80: ...5 12 Operation MN1902...
Page 98: ...7 12 Specifications MN1902...
Page 106: ...A 8 Accessories MN1902...
Page 122: ...Index MN1902...
Page 124: ...Comments MN1902 Thank you for taking the time to help us...
Page 125: ......