Basic Installation 3-15
MN1902
3.5 Motor connections
The motor can be connected directly to the FlexDrive
II
or through a motor contactor
(M-Contactor).
Location
Connector X1 / X1A
Part number
FDH
1
A...
FPH
1
A...
FDH
2
A...
FPH
2
A...
FDH
2
A
15
...
FPH
2
A
15
...
FDH
4
A...
FPH
4
A...
Nominal output voltage
160VDC
320VDC
320VDC
565/650V
Output voltage range
135-176VDC
306-350VDC
258-355VDC
254-746VDC
See
section
3.5.4
V
W
U
Motor
To earth/ground outer shield, use 360° clamps connected to backplane
Thermal
switch
A
B
Brake
(if present)
C
D
See
section
3.5.5
Unshielded
lengths should be
as short as
possible.
Optional motor
circuit contactors
Figure 7 - Motor connections
CAUTION
: Do not connect supply power to the FlexDrive
II
UVW outputs. The
FlexDrive
II
might be damaged.
CAUTION
: The motor leads U, V and W must be connected to their corresponding U,
V or W terminal on the motor. Misconnection will result in uncontrolled
motor movement.
The motor power cable must be shielded for CE compliance. The connector or gland used at
the motor must provide 360 degree shielding. The maximum recommended cable length is
30.5m (100ft).
Note:
For CE compliance the motor earth/ground should be connected to the drive
earth/ground.
Summary of Contents for Flex+DriveII
Page 1: ...FlexDriveII Flex DriveII Servo Controls SERVO DRIVE Installation Manual 10 02 MN1902...
Page 2: ......
Page 14: ...2 4 Introduction MN1902...
Page 68: ...4 20 Input Output MN1902...
Page 80: ...5 12 Operation MN1902...
Page 98: ...7 12 Specifications MN1902...
Page 106: ...A 8 Accessories MN1902...
Page 122: ...Index MN1902...
Page 124: ...Comments MN1902 Thank you for taking the time to help us...
Page 125: ......