INTRODUCTION
I-E96-213A
7 - 1
SECTION 7 - MAINTENANCE
INTRODUCTION
The Multi-Function Controller (IMMFC05) requires limited
maintenance. This section contains a maintenance schedule.
MAINTENANCE SCHEDULE
Perform the tasks in Table
at the specified intervals.
Table 7-1. Maintenance Schedule
Task
Interval
Clean and tighten all power and
grounding connections.
Every 6 months or during plant
shutdown, whichever occurs first.
Use a static safe vacuum cleaner
to remove dust from:
Modules
Module Mounting Unit
Fan Assembly
Power Entry Panel
Every 6 months or during plant
shutdown, whichever occurs first.