INSTALLATION
SETUP
I-E96-213A
3 - 3
NOTE: Jumpers J17-J22 are factory set (pins 1 and 2 jumpered) and
should not be changed. Jumpers J23 and J24 are intended for future
use. Their configuration does not matter at this time.
Figure 3-1. User Configured Switch Locations
Table 3-2. Switch SW4 Options
User
Settings
Switch
Position
Function
1
0*
Not used.
2
0*
Disable On-Line Configuration.
1
Enable On-Line Configuration.
3
0*
Not used.
4
0*
Perform ROM checksum routine.
1
Inhibit ROM checksum routine.
5
0*
Perform ROM check.
1
Inhibit ROM check.
6
0*
Compact configuration - moves configured blocks to the top of NVM
while moving free space to the bottom (this is known as compacting).
Leave switch OPEN; insert module into MMU. When front panel LEDs
1, 2, and 4 are ON, remove the module, put the switch in the CLOSED
position; reinsert the module. The MFC goes into the CONFIGURE
mode and with a compacted configuration.
1
7
0*
Initialize NVM (erase configuration). Leave switch OPEN; insert
module into MMU. When front panel LEDs 1, 2, and 4 are ON, remove
the module, put the switch in the CLOSED position; re-insert the
module. The module is now ready to be configured.
NOTE: This switch remains CLOSED for normal operation.
1
8
0*
Primary MFC.
1
Redundant MFC.
* Normal switch setting for normal module operation.
T00024A
P1
P2
P3
STATUS
LED
GROUP
LEDS
XU39
SW4
OPTIONS
SW3
MODULE ADDRESS
STOP
RESET
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8