INTRODUCTION
NOMENCLATURE
1 - 6
I-E96-213A
®
NOMENCLATURE
This list contains the nomenclature and functions of the equip-
ment used with the MFC.
Nomenclature of the Control and Slave Modules
Name
Nomenclature
Function
Analog Control Station
IISAC01 (L)
Provides the operator with single loop monitoring
and control.
Analog Slave Input
IMASI02 (L)
Supplies 15 analog inputs with a range from +10
to -10 VDC, 1 to 5 VDC, 4-20 mA, Smart
Transmitter interface.
Analog Output Station
IMASO01 (L)
Supplies 14 analog outputs, (1-5 VDC, 4-20 mA).
Control I/O Slave Module
IMCIS02 (L)
Supplies 4 analog inputs (4 to 20 mA, 1 to 5
VDC), 3 digital inputs (120 VAC, 125 VDC, or 24
VDC), 2 analog outputs (4 to 20 mA, 1 to 5 VDC),
and 4 digital outputs (24 VDC).
Digital Slave Input Module
IMDSI02 (L)
Supplies 16 contact inputs of 24 VDC, 125 VDC,
or 120 VAC
Pulse Counter
IMDSM04 (H)
Supplies 8 input channels that determine the
count, frequency, or period of pulse or sine wave
inputs.
Digital Slave
IMDSM05 (H)
Interfaces the MFC to up to 8 Digital Logic
Stations.
Digital Slave Output Module
IMDSO01 (L)
IMDSO02 (L)
IMDSO03 (L)
IMDSO04 (L)
Supplies 8 solid state relay outputs of 24 VAC to
240 VAC.
Supplies 8 solid state relay outputs of 4 VDC to 50
VDC.
Supplies 8 solid state relay outputs of 5 VDC to
160 VDC.
Supplies 16 open collector outputs of 24 VDC.
Remote I/O
IMRIO02 (L)
Acts as the interface between remote slaves
located up to 10,000 feet away.
NOTE:
(L) denotes low power slave; (H) high power slave. Low power slaves use HCMOS and semi-custom integrated
circuits to reduce power consumption.