INSTALLATION
PHYSICAL INSTALLATION
I-E96-213A
3 - 5
To reverse INFI-NET protocol or time stamping, do operation 2
again.
1. Set switch S4 pole 1 to the 1 position.
2. Set poles 2 through 6 per Table
3. Insert the module in its slot in the module mounting unit
(refer to Installing Modules).
4. When the special operation is complete, the Status LED
turns red and LEDS 1 through 6 illuminate.
5. Remove the module.
6. Reset pole 1 to the 0 position.
7. Reset poles 2 through 6 per Table
.
8. Insert the module in its slot. It will enter its normal operat-
ing mode.
PHYSICAL INSTALLATION
When the preceding steps have been completed, the MFC is
ready to be installed in the Module Mounting Unit (MMU). To
insert the MFC:
1. Verify the slot assignment of the module.
Table 3-3. Switch SW4 Special Operations
Pole
Value
1
128
2
64
3
32
4
16
5
8
6
4
7
2
8
1
Special
Operation
Description
1
0
0
0
0
0
0
0
0
Reserved. Do not use. If you use this
setting your module may not operate
properly.
1
1
0
0
0
0
0
0
1
Reserved for future options. Not used at this
time.
1
0
1
0
0
0
0
0
2
Initialize NVRAM configuration space.
1
1
1
0
0
0
0
0
3
Reserved. Do not use. If you use this
setting your module may not operate
properly.
1
0
0
1
0
0
0
0
4
INFI-NET protocol enable. This allows the
MFC to take advantage of INFI-NET/
Superloop capabilities.
1
1
0
1
0
0
0
0
5
Permit segment modification (allows
change to segment scheme configured with
Function Code 82 specification S1).
1
0
1
1
0
0
0
0
6
Enable time stamping. This operation
instructs the MFC to generate time
information with point data. It is applicable
only to INFI-NET/Superloop systems.