INSTALLATION
SETUP FOR COMMUNICATION HIGHWAY ENVIRONMENT
3 - 4
I-E96-213A
®
SETUP FOR COMMUNICATION HIGHWAY ENVIRONMENT
INFI-NET/Superloop
To configure the MFC for use in the INFI-NET/Superloop envi-
ronment, follow Steps 1 through 4.
1. Set dipswitch SW 4 poles 1 and 4 in the OFF (open/logic 1).
All other poles must be in the ON (closed/logic 0) position.
Doing so does not modify the configuration.
2. Reset the module. The Status LED turns red and LEDs 1
through 6 illuminate.
3. Set dipswitch SW 4 back to its original (or permanent
setting).
4. Reset the module.
Plant Loop
To configure the MFC for use in the Plant Loop environment,
follow Steps 1 through 5.
1. Set dipswitch SW4 with poles 1 and 3 in the OFF (open/
logic 1) position to perform a default MFC format operation. All
remaining poles must be in the ON (closed/logic 0) position.
NOTE: This Step
DELETES the configuration and all files.
2. Reset the module. The Status LED turns red and LEDs 1
through 6 illuminate.
3. Set dipswitch SW 4 to its original (or permanent setting).
4. Reset the module.
5. Reload Plant Loop Environment configuration.
SPECIAL OPERATIONS
The special operations feature which allows you to configure
the MFC to do a one-time special operation rather than enter-
ing its normal mode of operation. Steps 1 through 8 explain
how to set the MFC for special operations and reset it for nor-
mal operation. Table
shows the switch settings and
explains each special operation.
Special operation 2 should be done as the first step of installa-
tion. If you are installing the MFC in an INFI-NET or Superloop
environment, do special operation 4 next. If you desire time
stamping, next do special operation 6.