TROUBLESHOOTING
STATUS WORD DISPLAYS
I-E96-213A
6 - 5
STATUS WORD DISPLAYS
Module status words are listed in Table
. These words pro-
vide detailed information on MFC error conditions. Any of the
INFI 90 operator interface devices can be used to access these
words. Refer to the product instruction for your specific inter-
face device for details.
Module Address
28
0 0 1 1 1 0
Yes
Monitors SW 3; displays the selected address
on front panel LEDs.
Reset Button
29
1 0 1 1 1 0
No
None.
Stop Button
30
0 1 1 1 1 0
No
Test interrupt; displays 3F hex (LEDs 1 - 6
illuminate).
MFC Mode Pri-
mary
32
0 0 0 0 0 1
No
Successful completion; displays 55 hex on
front panel LEDs. Requires NKMF02 cable
between primary and secondary. Also
requires IMDSM05 digital slave. (Refer to
in this Section).
MFC Mode Sec-
ondary
33
1 0 0 0 0 1
Yes
Displays count of messages received.
Table 6-2. Diagnostic Test IDs
(continued)
Test Name
Test
ID
SW4
Switch Settings
1 2 3 4 5 6
Continuous
Comments
Table 6-3. Digital Slave Setup
for Diagnostic IDs
Switch
Pole
1 2 3 4 5 6 7 8
Enable
X 1
Address Module
X X 0 0 1 1 1 1
Configuration
1 1 0 X
NOTES:
X = does not matter
Jumper J17 - pins 2 and 3
Jumper J18 - pins 2 and 3