INSTALLATION
SETUP
3 - 2
I-E96-213A
®
5. Store the module in an environment of good air quality,
and free from temperature and moisture extremes.
SETUP
Module Address - Switch SW3
Switch SW3, an eight pole dipswitch, is the module address
switch. Poles 4 through 8 set the address. Note that pole 4 has
a binary weight of 16, while pole 8 has a weight of 1. A pole in
the open position is a logic 1; closed logic 0. Valid module
addresses are 2 through 31 (refer to Table
for address
switch settings). See Figure
for switch location.
NOTE: Pole 1
MUST BE in the open position, otherwise the MFC
will not function properly. Pole 2 in the open position puts the mod-
ule in the diagnostic mode; closed the normal execution mode. Pole
3 setting does not matter.
Options - Switch SW4
Switch SW4, the Option switch, is used to select various
optional routines. Table
lists the settings and routines. See
Figure
NOTES:
1.
When redundancy is used, switches 1 through 7 on the redun-
dant MFC are set the same as the primary MFC.
2.
Record your settings in the USER SETTINGS column.
Table 3-1. Switch SW3 Module Address
Address
Switch
Position
1 2 3 4 5 6 7 8
Address
Switch
Position
1 2 3 4 5 6 7 8
Address
Switch
Position
1 2 3 4 5 6 7 8
2
1 0 X 0 0 0 1 0
12
1 0 X 0 1 1 0 0
22
1 0 X 1 0 1 1 0
3
1 0 X 0 0 0 1 1
13
1 0 X 0 1 1 0 1
23
1 0 X 1 0 1 1 1
4
1 0 X 0 0 1 0 0
14
1 0 X 0 1 1 1 0
24
1 0 X 1 1 0 0 0
5
1 0 X 0 0 1 0 1
15
1 0 X 0 1 1 1 1
25
1 0 X 1 1 0 0 1
6
1 0 X 0 0 1 1 0
16
1 0 X 1 0 0 0 0
26
1 0 X 1 1 0 1 0
7
1 0 X 0 0 1 1 1
17
1 0 X 1 0 0 0 1
27
1 0 X 1 1 0 1 1
8
1 0 X 0 1 0 0 0
18
1 0 X 1 0 0 1 0
28
1 0 X 1 1 1 0 0
9
1 0 X 0 1 0 0 1
19
1 0 X 1 0 0 1 1
29
1 0 X 1 1 1 0 1
10
1 0 X 0 1 0 1 0
20
1 0 X 1 0 1 0 0
30
1 0 X 1 1 1 1 0
11
1 0 X 0 1 0 1 1
21
1 0 X 1 0 1 0 1
31
1 0 X 1 1 1 1 1
NOTE:
X = Setting does not matter.