INSTALLATION
PHYSICAL INSTALLATION
3 - 6
I-E96-213A
®
2. If your configuration requires a cable, connect the hooded
end of the cable to the rear of the MMU slot to be occupied by
the MFC. Connect the other end of the cable to the termination
unit (or termination module).
3. Verify that the dipshunts (supplied with the slave modules)
are installed to maintain Slave Expander Bus continuity.
4. Guide the top and bottom edges of the circuit card along
the top and bottom rails of the MMU.
5. Slide the module into the slot; push until the rear edge is
firmly seated in the backplane connectors. Lock the module in
place by turning the two captive screws on faceplate. The mod-
ule is in place when the notch on each screw is vertical and the
open end is pointing toward the center of the module.
6. Connect the hooded end of the cable from the NTMF01 Ter-
mination Unit (or NIMF01 Termination Module) to the P3 card
edge connector of the MFC.
The green Status LED should illuminate. If it does not, refer to
.
The module is now ready to be configured. Follow the steps in
.
WARNING
Disconnect power before installing dipshunts for slave mod-
ules on the MMU backplane (slave expander bus). Failure to do
so could result in severe or fatal shock.
AVERTISSEMENT
Couper l'alimentation avant d'installer les dipshunts sur la
plaque arriere du chassis de montage de modules (MMU).
Toute negligence a cet egard constitue un risque de choc pou-
vant entrainer des blessures graves, voire moretlles.