CONFIGURATION
FUNCTION CODES
4 - 6
I-E96-213A
®
Function Code 82 - Segment Control
Function Code 82, Segment Control, is permanently assigned
to block 15 and occupies the next four consecutive blocks. The
Segment Control block is used to divide the set of function
blocks into subsets (or segments), and specify the operating
parameters for each segment individually. The Segment Block
has 5 outputs that can be used as inputs to other blocks. The
MFC supports a maximum of eight Segment Control Blocks.
The seven additional Segment Control blocks can be placed in
any user configurable block. Refer to Tables
and
.
Table 4-4. Function Code 82 Specifications
Spec.
No.
Tune*
Default
Value
Data Type
Range
Min. Max.
Description
S1
No
1
Int(2)
1 to 2
Segment Attributes Tune Lock and Time Units
Tune Lock
0X = Tuning allowed
1X = Tuning not allowed
Time Units
X1 = Seconds
X2 = Minutes
S2
Yes
.250
Real(3)
Full
Target period (seconds/minutes)
S3
No
0
Int(2)
0 to 32,767 Segment priority (0 = lowest)
S4
No
1
Int(2)
0 to 32,767 Checkpoint period (number of cycles per
checkpoint)
S5
No
0
Int(1)
0 to 1
PID reset mode
0 = normal
1 = external
S6
No
10.000
Real(3)
Full
PID maximum derivative gain
S7
No
1.000
Real(3)
0.0 to
9.2E18
Minimum report time for all exception reports
in this segment (in seconds)
S8
No
60.000
Real(3)
0.0 to
9.2E18
Maximum report time for all exception reports
in this segment (in seconds)
S9
No
2.000
Real(3)
0.0 to
9.2E18
Significant change parameter for all loop (i.e.,
Station) exception reports in this segment (in
% of span)
S10
No
1.000
Real(3)
0.0 to
9.2E18
Alarm deadband for all high/low alarm reports
in this segment (in % of span)
S11
No
1.000
Real(3)
0.0 to
9.2E18
Alarm deadband for all deviation alarm reports
in this segment (in % of span)
S12
No
0.0
Real(3)
Full
Reserved