In addition, the entire status information of the device and the maximum indicators of the two
sen.sor values and the internal temperature are available.
Transducer Block “ADVANCED DIAGNOSTIC”
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Corrosion
detec-tion
(CORROSION_
DETECTION)
AUTO - OOS
OFF: Corrosion detection off
ON
: Corrosion detection on
Note:
Only possible for RTD 4-wire connection and
thermocouples (TC).
Sensor drift
mon-itoring
(SENSOR_DRIFT_
MONITORING)
AUTO - OOS
Deviation between SV1 and SV2 as error (Failure) or
as need for mainte-nance (Maintenance):
OFF: Sensor deviation monitoring off
FAILURE: (sensor deviation > SENSOR_
DRIFT_LIMIT) => Failure
MAINTENANCE: (sensor deviation >
SENSOR_DRIFT_LIMIT) => Maintenance
Sensor drift mode
(SENSOR_DRIFT_
MODE)
AUTO - OOS
Select whether a status is generated if the value set in
the SENSOR_DRIFT_LIMIT parameter is undershot
(Undershooting) or over-shot (Overshooting).
Note:
If “Overshooting” is selected, the corresponding
status is generated if the limit value is overshot
(SENSOR_DRIFT_LIMIT). In the case of
“Under-shooting”, the status is output if the
limit value is undershot.
Sensor Drift alert
value (SENSOR_
DRIFT_ALERT_
VALUE)
AUTO - OOS
Limit value of the permitted deviation from 1 to
999.99.
System alarm
delay (SYSTEM_
ALARM_DELAY)
AUTO - OOS
Alarm hysteresis: Value as to the time a device status
(Failure or Mainte-nance) and measured value status
(Bad or Uncertain) is delayed until the status is
output. Can be configured between 0 and 10 seconds
Note:
This setting does not affect the display.
Ambient temp.
alarm (AMBIENT_
ALARM)
AUTO - OOS
Maintenance or Failure in the event of the operating
temperature of the transmitter being undershot or
overshot (< -40 °C (-40 °F) or > +85 °C (185 °F)):
Maintenance: Int. temperature overshoot/
undershoot results in mes-sage.
Failure: Int. temperature overshoot/undershoot
results in 'Failure' device status.