39
Cate-
gory
No.
Status messages
- ACTUAL_STATUS_NUMB
ER in the 'Advanced
Diagnostics' Transducer
Block .
- Local display
Error messages in the
Sensor Transducer Block
in question
Sensor
Transducer Block
measured value
status
Cause of error / remedy
Output
variables
affected
F- 041
Device status message (FF):
Sensor break
F-041
Local display:
F-041
BLOCK_ERR =
Other
|
Input Failure
|
Device needs
maintenance now
QUALITY = BAD Cause of error:
1. Electr. interruption of sensor or
sensor wiring
2. Incorrect setting for type of
connection in the SENSOR_
CONNECTION parameter
Remedy:
Re 1.) Reestablish electr. connection
or replace sensor.
Re 2.) Configure correct type of
connection.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_error =
Mechanical failure
SUBSTATUS =
Sensor failure
F- 042
Device status message (FF):
Sensor corrosion
F-042
Local display:
F-042
BLOCK_ERR =
Other
|
Input Failure
|
Device needs
maintenance now
QUALITY = BAD Cause of error:
Corrosion detected on the sensor
terminals.
Remedy:
Check wiring and replace if
necessary.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_error =
Mechanical failure
SUBSTATUS =
Sensor failure
M-
042
Device status message (FF):
Sensor corrosion
M-042
Local display:
M-042 ↔ Measured value
BLOCK_ERR =
Device needs
maintenance now
QUALITY =
UNCERTAIN
Cause of error:
Corrosion detected on the sensor
terminals.
Remedy:
Check wiring and replace if
necessary.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_Error =
No error
SUBSTATUS =
Sensor conversion
not accurate
F-
043
Device status message (FF):
Sensor shortcut
F-043
Local display:
F-043
BLOCK_ERR =
Other
|
Input Failure
|
Device needs
maintenance now
QUALITY = BAD Cause of error:
Short circuit detected at the sensor
terminals.
Remedy:
Check sensor and sensor wiring.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_error =
Mechanical failure
SUBSTATUS =
Sensor failure
F-
101
Device status message (FF):
Under-usage of sensor range
F-101
Local display:
F-101
BLOCK_ERR =
Other
|
Input Failure
|
Device needs
maintenance now
QUALITY = BAD Cause of error: Physical measuring
range undershot.
Remedy:
Select suitable sensor type.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_Error =
General error
SUBSTATUS =
Sensor failure
M- 101
Device status message (FF):
Under-usage of sensor range
M-101
Local display:
M-101 ↔ Measured value
BLOCK_ERR =
Device needs
maintenance now
QUALITY =
UNCERTAIN
Cause of error:
Physical measuring range undershot.
Remedy:
Select suitable sensor type.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_Error = No
error
SUBSTATUS =
Sensor conversion
not accurate
F- 102
Device status message (FF):
Exceedence of sensor range
F-102
Local display:
F-102
BLOCK_ERR =
Other
|
Input Failure
|
Device needs
maintenance now
QUALITY = BAD Cause of error:
Physical measuring range overshot.
Remedy:
Select suitable sensor type.
SV1, SV2 also
PV1, PV2
depending
on the
configuration
Transducer_Error =
General error
SUBSTATUS =
Sensor failure