Transducer Block “ADVANCED DIAGNOSTIC”
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Actual status
category / Previous
status category
(ACTUAL_STATUS_
CATEGORY /
PREVIOUS_STATUS_
CATEGORY)
Read only /
AUTO - OOS
Current/last status category
Good: No errors detected
F: Failure: Error detected
M: Maintenance: Maintenance necessary
C: Service mode: Device is in the service mode
S: Out of Spec.: Device is being operated outside
the specifications
Actual status
number / previous
status number
(ACTUAL_STATUS_
NUMBER /
PREVIOUS_STATUS_
NUMBER)
Read only /
AUTO - OOS
Current/past status number:
000 NO_ERROR: No error is present
041 SENSOR_BREAK: Sensor rupture
043 SENSOR_SHORTCUT: Sensor short circuit
042 SENSOR_CORROSION: Corrosion of
connections or sensor cables
101 SENSOR_UNDERUSAGE: Measured value of
the sensor is below the linearization range
102 SENSOR_OVERUSAGE: Measured value of the
sensor is above the linearization range
104 BACKUP_ACTIVATED: Backup function
activated due to sensor failure
103 DEVIATION: Sensor drift detected
501 DEVICE_PRESET: Reset routine in progress
411 UP-/DOWNLOAD: Uploading/downloading
482 SIMULATION: Device is in the simulation mode
402 STARTUP: Device is in the startup/initialization
phase
502 LINEARIZATION: Linearization incorrectly
selected or configured
901 AMBIENT_TEMPERATURE_LOW: Ambient
temperature too low; RJ_Value < -40 °C (-40 °F)
902 AMBIENT_TEMPERATURE_HIGH: Ambient
temperature too high; RJ_Value > 85 °C (185 °F)
261 ELECTRONICBOARD: Electronics module/
hardware faulty
262 DISPLAY_COMMUNICATION_FAILURE: No
communication possible between the display and
transmitter
431 NO_CALIBRATION: Calibration values lost/
modified
283 MEMORY_ERROR: Contents of memory
inconsistent
221 RJ_ERROR: Error in reference junction
measurement/internal temperature measurement