74
Transducer Block “Sensor 1 and 2”
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Primary value
max. indicator
(PV_MAX_
INDICATOR)
AUTO - OOS
Max. indicator for PV is stored in the nonvolatile
memory in intervals of 10 minutes. Can be reset.
Primary value min.
indicator
(PV_MIN_
INDICATOR)
AUTO - OOS
Min. indicator for PV is stored in the nonvolatile
memory in intervals of 10 minutes. Can be reset.
Sensor value
(SENSOR_
VALUE)
Dynamic /
read only
Sensor Transducer 1:
VALUE = Value of the sensor connected to the S1
terminal group
STATUS = Status of this value
Sensor Transducer 2:
VALUE = Value of the sensor connected to the S2
terminal group
STATUS = Status of this value
Sensor type
(SENSOR_TYPE)
AUTO - OOS
Configuration of the sensor type.
Sensor Transducer 1: Settings for sensor input 1
Sensor Transducer 2: Settings for sensor input 2
Note: Please observe the wiring diagram in Section
3.1 when connecting the individual sensors. In
the case of 2-channel operation, the possible
connection options in Section 3.2 also have to
be observed.
Sensor connection
(SENSOR_
CONNECTION)
AUTO - OOS
Sensor connection mode:
Sensor Transducer 1:
2-wire
3-wire
4-wire
Sensor Transducer 2:
2-wire
3-wire
Sensor range
(SENSOR_
RANGE)
Read only
(EU_100, EU_0)
AUTO - OOS
(UNITS_IND
EX, DECIMAL)
Physical measuring range of the sensor:
EU_100 (upper sensor range limit)
EU_0 (lower sensor range limit)
UNITS_INDEX (unit of the SENSOR_VALUE)
DECIMAL (places after the decimal point for the
SENSOR_VALUE.
This does not affect the measured value display.)
Sensor offset
(SENSOR_
OFFSET)
AUTO - OOS
Offset of the SENSOR_VALUE The following values
are permitted:
-10 to +10 for Celsius, Kelvin, mV and Ohm
-18 to +18 for Fahrenheit, Rankine