background image

Masoneilan

8000 Models

Electro-pneumatic 

Positioners and Transducers 

ATEX Instruction Manual (Rev. A)

Baker Hughes Data Classification : Public

Содержание Masoneilan 8000

Страница 1: ...Masoneilan 8000 Models Electro pneumatic Positioners and Transducers ATEX Instruction Manual Rev A Baker Hughes Data Classification Public...

Страница 2: ...eter 10 6 Electrical Characteristics 10 6 1 Intrinsically safe apparatus 10 6 2 Flameproof Apparatus 11 7 Pneumatic Connections 11 8 Electrical Connection Installation and Start Up 12 8 1 Conduit Entr...

Страница 3: ...E SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE...

Страница 4: ...talled put into service and maintained by qualified and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmosphere Such traini...

Страница 5: ...matic signal in the 207 to 1035 mbar 3 to 15 psi or 414 to 2070 mbar 6 to 30 psi ranges as appropriated Generally speaking a signal from the Model 8007 057 is used by a pneumatic positioner or a suppl...

Страница 6: ...87 88 actuators without cam 1 37 38 and 87 88 actuators basic cam 2 Camflex II multi lobe cam 3 Sigma F multi lobe cam 4 Minitork II 38002 multi lobe cam 5 36000 Control Ball Valves multi lobe cam 6 H...

Страница 7: ...l 55 C to 80 C 8008 20 C to 80 C Storage and transportation 55 C to 90 C Air supply and output range Transducer PRESSURE in bar psi Air supply Output signal range 8007 1 586 23 0 207 to 1 035 3 to 15...

Страница 8: ...t Pierre CS40087 14110 CONDE SUR NOIREAU FRANCE Type designation 8007 058 or 8008 058 Electropneumatic transducers 8013 58 Electropneumatic positioners the can take the values from 0 to 9 Basic and co...

Страница 9: ...ved per EN 60079 11 Maximum input characteristics at terminal block Ui V Ii A Pi W Li H Ci nF 28 0 1 0 7 0 0 5 ATEX Flameproof Marking and Electrical Safety Parameters 5 1 Marking Name and address of...

Страница 10: ...STATIC DISCHARGES SEE INSTRUCTIONS DO NOT OPEN IF AN EXPLOSIBLE ATMOSPHERE MAY BE PRESENT Cable temperature Must be mentioned if the temperature is greater than 70 C T Ambient T Cable 70 C 86 C 80 C 9...

Страница 11: ...14 15 150 94 BLUE 15 10 110 35 135 BLUE 16 0 10 701 2901 YELLOW 20 0 20 503 BLUE 21 0 20 248 BLUE 22 2 10 1000 YELLOW 23 7 Pneumatic Connections Make sure that the air supply pressure is suitable for...

Страница 12: ...check the cover is fully screwed with the four screws 1 Screws up to surface contact then add to turn more Note Before installation check that the device is undamaged In the event of damage inform th...

Страница 13: ...gulation for electrical installation Connector slot approval Insulation must be free of any damage along the wires inside the housing Tightening must be sufficient to bring constant contact in time wi...

Страница 14: ...the user responsibility to check the installation against Intrinsic safety rules taking into account entity parameters of all devices in the loop in addition of temporary one like measurement devices...

Страница 15: ...ully read the following safety warnings Comply with current national and local regulations for electrical installation work Must be installed and put into service in conformance with EN 60079 14 and o...

Страница 16: ...ated When shipped alone the calibration will be made as follows Proceed with pneumatic and electrical connections as per 6 and 7 Check the position of the balance spring 8 as a function of the actuato...

Страница 17: ...ust be cleaned to prevent any dust build up on the walls See instruction 12 1 b c for safe cleaning Check that no part of the transducer or positioner is damaged In the event of damage replace the def...

Страница 18: ...evice are free of potentially explosive atmosphere c To avoid the risk of ignition from electrostatic discharge it shall be necessary to follow the guidance of EN 60079 32 1 for example to clean the d...

Страница 19: ...h the minimum temperature written on the serial plate For the 8000 Series housing in aluminum material the user will have to determine the use of the device for group II category 1 zone 0 against pote...

Страница 20: ...r must choose a cable entry and a cable compatible with Ambient Temperature Cable Temperature 70 C 86 C 80 C 96 C When the ambient temperature is lower than 20 C the user will have to choose a cable e...

Страница 21: ...Masoneilan 8000 Models Positioners and Transducers ATEX Manual 21 2021 Baker Hughes Company All rights reserved NOTES...

Страница 22: ...22 Baker Hughes 2021 Baker Hughes Company All rights reserved NOTES...

Страница 23: ...Masoneilan 8000 Models Positioners and Transducers ATEX Manual 23 2021 Baker Hughes Company All rights reserved NOTES...

Страница 24: ...com Copyright 2021 Baker Hughes Company All rights reserved Baker Hughes provides this information on an as is basis for general information purposes Baker Hughes does not make any representation as t...

Отзывы: