Troubleshooting the System
© 1999, AXCESS
TM
Inc.
750.001.003
Revised June 1999
91
Check the Output and Connections to Third-Party Devices
If the transmission and reception portions of the system seem fine,
but the output is incorrect or absent, check the connections to the
devices that receive system output.
Serial Reader
Step 1:
Ensure that the communication port settings are correct:
Baud Rate
4800
Data Bits
8
Parity
None
Stop Bits
1
Flow Control None
Wiegand Reader
Step 1:
Ensure that the Wiegand control panel is SIA 26-bit
standard compliant.
Step 2:
Ensure that Data Zero, Data One and Ground are wired to
the Wiegand control panel correctly.
Step 3:
Ensure that the Tags and site code are entered correctly
into the panel.
FTT Reader
Step 1:
Ensure that the Reader is not in diagnostics mode.
Step 2:
Ensure that the LonWorks wiring is correct.
Step 3:
Ensure that Serial Gateway is connected to the PC and
that the communication port settings are correct:
Baud Rate
2400
Data Bits
8
Parity
None
Stop Bits
1
Flow Control None