Troubleshooting
56
Avaya
t
RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual
S
164201543 Rev A
When this happens, follow these steps:
1.
Observe the display to see which alarm is active.
NOTE
To find out if more than one alarm is active, press . This switches the display
between alarm messages. To silence the audible alarm, press button (A) below the
display.
2.
Find the alarm message in Table 13 or Table 14 and follow the
instructions to resolve the problem. To clear an alarm after
resolving the problem, press button (B) below the display. If
the problem is still present, the alarm will sound again after a
short delay.
Table 13 contains descriptions of critical alarm messages. Critical alarms
require immediate operator attention and corrective action.
Table 13. Critical Alarm Messages
Alarm Message
What It Means
What to Do
A Low Battery
The UPS has shut down after running
on battery and discharging the
batteries.
Wait for AC input power to be restored. When AC input
power returns, the UPS begins recharging batteries and
applies power to the load.
C High Battery
The battery voltage is too high
because of a charger problem,
battery problem, or incorrect
parameter setting.
Contact your Avaya service representative.
E Low AC Output
The UPS has shut down because the
AC output voltage is too low to
provide power to the load.
Contact your Avaya service representative.
F High AC Output
The UPS has shut down because the
AC output voltage is too high.
Contact your Avaya service representative.
S High AC Input
The AC input voltage is too high; any
further increase to the voltage may
damage the UPS.
This alarm automatically clears when input voltage
returns to normal limits. The UPS will continue to support
the load until the batteries are depleted.
G Output Overload
The load is requiring more power
than the UPS power modules are
capable of supplying, and the UPS
has switched to Bypass mode.
Switch off your equipment one piece at a time until the
alarm stops.
I Overload Shutdown
The UPS has shut down due to
excessive load.
Remove excess load(s) from the UPS output and restart
the UPS by pressing the ON button through the front
panel display.