Electrical Installation
14
Avaya
t
RS9 UPS (9–18 kVA, 9-Slot Models) Site Preparation, Installation and Operator’s Manual
S
164201543 Rev A
Entrance Panel
Wiring Access Hole
for Optional EPO
Wiring Access Hole
for an Optional
Generator Input
Signal
Figure 7. UPS Power Entrance Panel and Wiring Knockouts
2.
Remove the knockouts in the entrance panel for AC input and
AC output wiring.
3.
Install the conduit adapters. AC input and AC output
conductors must be run through separate conduits. UPS output
circuits must be installed in dedicated conduit systems and not
shared with other electrical circuits.
4.
Torque the screws holding all input and output power
conductors to the values specified in Table 2 on page 12.