- 35 -
(
Picture 1
)
Anti-cold wind function when compressor stops
:
①
When TE is in the fall status, if TE>30
℃
,the indoor fan runs at low fan
speed;TE30
≤
℃
,indoor fan turns off;
②
When TE is in the rise status, if TE35
≥
℃
, the indoor fan runs at low fan speed; TE35<
℃
,
indoor fan turns off;
(
Picture 2
)
Residual-heat removing function after air-conditioner stops
:
When TE
>
35
℃,
the indoor fan runs at the low fan speed, if
≤
35
℃
,the indoor fan turns off,
and air-conditioner stops for starting the process of residual heat removal and last for
≤
10seconds, within the 10second of process of residual heat removal, if TE< 35
℃
, the indoor
fan turns off at once.
⑾
Anti-high temperature protection
:
①
when run on Heating mode
,
if TE
≥
57
℃
and continuously last 10 seconds, the outdoor fan
stops; if TE
≥
64
℃
and last for 10s
,
the compressor stops again
;
When TE< 52
℃
and
satisfying 3minutes protection delay condition, the compressor resume normal work.
。
②
Such temperature protection is valid only if the TE sensor works normally.
⑿
The defrosting function under heating mode
①
When the outdoor sensor in good condition, the defrosting process starts, and the sleeping
Summary of Contents for ASW-H09A4/EAR1-dw
Page 1: ...For model ASW H09A4 EAR1 dw ASW H12B4 EAR1 dw ASW H18B4 EAR1 dw ASW H24B4 EAR1 dw ...
Page 6: ... 4 Remote Controller Instructions ...
Page 7: ... 5 ...
Page 8: ... 6 ...
Page 9: ... 7 ...
Page 10: ... 8 ...
Page 11: ... 9 ...
Page 12: ... 10 ...
Page 13: ... 11 ...
Page 14: ... 12 ...
Page 48: ... 46 ...
Page 68: ... 68 Exploded Pictures 1 Indoor unit exploded picture 7K 9K 12K BTU E Series ...
Page 70: ... 70 2 Outdoor unit exploded picture 7K 9K 12K BTU E Series ...
Page 72: ... 72 3 Indoor unit exploded picture 18K 24K BTU E Series ...
Page 74: ... 74 4 Outdoor unit exploded picture 18K 24K BTU E Series ...
Page 76: ......