- 25 -
if TE< TE8, the indoor fan stops immediately.
⑩
Overheated protection
:
a) When heating function runs
,
if TE
≥
TE9 and last for 10seconds
,
the outdoor fan stops
;
if
TE
≥
TE10 and last for 10seconds, then stop the compressor
;
When TE< TE11 and after the 3
minutes protection delay, the compressor resumes normal working.
b) This temperature protection is valid only when the TE temperature sensor runs normally.
(8)The auxiliary electric heating function
①
The electric heating function may not start unless the heating mode runs normally e.g. the
compressor starts, the outdoor fan runs, the four-way valve is electrified, the indoor fan is on
as well as the availability of the below conditions:
a)TE < TE12
;
b)TA < TA3
;
c)TS – TA
≥
3
℃;
d)The compressor runs continuously in heating mode for 4min
;
②
The auxiliary electric heating may withdraw working if meet one of the below conditions:
a)TA > TA3
;
b)TS – TA < 2
℃;
c)TE > TE11
;
③
If one of the compressor, four-way valve and indoor fan doesn’t work or there is error
feedback from the indoor fan, the auxiliary electric heating withdraw from work;
④
If the sensor of TE is damaged and the turn-off without non-electricity occurred in the
ongoing auxiliary electric heating process, the indoor fan turns in the low speed wind
operation for 40 seconds and stops
;
(9)Intelligent defrosting function
①
Under the operation of the intelligent defrosting mode, the air-conditioner starts the
defrosting process if satisfying the requirement of one of the below five conditions (the
sub-conditions included shall all be satisfied). During the defrosting process, the sleeping light
is twinkling:
●
a) The outdoor fan starts the overloading protection and the outdoor fan stops;
b) Restart the outdoor fan after stop and the continuous running time over than 10
minutes;
c)The accumulated operation time of the compressor
≥
45min
;
d)The continuous operation time of the compressor
≥
20min
;
e)TE
≤
TE12
。
●
a) After the 5 minutes operation of the heating mode or 5 minutes later after the defrosting
process, starts the capture motion for the max. difference value between TE and TA, when
the difference between TE and TA being reduced up than X min and the time lasts
≥
3min
;
b)The continuous operation time of the compressor
≥
5min
;
c)The accumulated operation time of the compressor
≥
45min
;
d)TE
≤
TE12
;
Note
:
When the wind speed correction available, if the wind speed of the indoor fan drops by
one gear, the temperature difference correction value shall be -1
℃,
if the wind speed of the
indoor fan rises by one gear, the temperature difference correction value shall be +1
℃
.
●
a)The accumulated operation time of the compressor
≥
3hour
;
Summary of Contents for ASW-H09A4/EAR1-dw
Page 1: ...For model ASW H09A4 EAR1 dw ASW H12B4 EAR1 dw ASW H18B4 EAR1 dw ASW H24B4 EAR1 dw ...
Page 6: ... 4 Remote Controller Instructions ...
Page 7: ... 5 ...
Page 8: ... 6 ...
Page 9: ... 7 ...
Page 10: ... 8 ...
Page 11: ... 9 ...
Page 12: ... 10 ...
Page 13: ... 11 ...
Page 14: ... 12 ...
Page 48: ... 46 ...
Page 68: ... 68 Exploded Pictures 1 Indoor unit exploded picture 7K 9K 12K BTU E Series ...
Page 70: ... 70 2 Outdoor unit exploded picture 7K 9K 12K BTU E Series ...
Page 72: ... 72 3 Indoor unit exploded picture 18K 24K BTU E Series ...
Page 74: ... 74 4 Outdoor unit exploded picture 18K 24K BTU E Series ...
Page 76: ......