13
6.2 When the air conditioner is powered on, the outdoor fan, four- way
valve and compressor will start at the same time while when it is
shut down, the outdoor fan and compressor will be shut down at the
same time and so will the four- way valve after 2 minutes' delay.
6.3 Under the mode of heating, the compressor can not be shut down
within 3 minutes after it is powered on unless the operation mode is
changed or the air conditioner is turned off.
6.4 There is a 3 temperature compensating function. The temperature
measured at the in-blow vent minus 3 automatically can be
regarded as that compared with the temperature set (This function
does not exist under other circumstances).
6.5 According to the temperature set, the condition upon which the
compressor will be switched on is indoor temperature
≤
temperature
set-1 While the condition upon which it will be switched off
is indoor temperature is indoor temperature
≥
tempe 1 .
When the indoor temperature is equal to that set, the original
operation mode will be kept.
6.6 Indoor fan control:
6.6.1 Heating operation and prevention of cold wind
When the compressor works:
1.
During the rising process of the temperature of coiled pipe,
the indoor fan will not start if the temperature of the coiled
Summary of Contents for ASW-07B4/HSAR
Page 1: ......
Page 7: ...Operation Hints ...
Page 8: ......
Page 9: ......
Page 33: ......
Page 35: ...Chapter 5 Main Technical Data ...
Page 42: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Page 61: ...Operation Hints ...
Page 62: ......
Page 63: ......
Page 93: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Page 112: ...6 60 detachable cool warm type 70 detachable cool warm type ...
Page 113: ...7 Operation Hints ...
Page 114: ...8 ...
Page 146: ...40 4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...